Circuit Protection

Frequently asked questions

Yes you can, as long as the correct type of fuse is selected, which can be source from a reputable wholesaler.

Our current G06 range will be compatible as long as 3mm is cut off the end of the comb busbar.

No our 2 pole RCCB/RCD’s can be wired with the line or load in the top or bottom and or with the live/neutral in the left/right terminals. The 4 pole RCCB’RCD’s can also be wired with the line or load in the top or bottom.

Yes the part number is RCD10-63/30/2ALV. RCD’s are voltage dependant due to the tripping coil inside rather like getting the correct voltage for a relay or contactor.

To eliminate the building wiring being at fault please disconnect completely the load side and re-test in isolation, check your device is testing the correct class or RCD and replace the batteries. If you have a number of units failing there has got to be something else wrong. Any more problems please call our technical for further help.

Yes, but not all other brands of RCD’s test switches might not operate; this is due to the wiring of the test resistor inside being wired between phase and neutral or phase and phase. All of Lewden’ s 4 pole devices test resistors are connected between phase and phase so will work without a neutral.

Back to the categories