WEATHER PROTECTION

IP CODES

IP codes signify the extent to which a product is protected against water or solid objects or dust getting through the exterior of the product and affecting its performance. IP stands for International Protection.

The IP codes are defined in IEC standard IEC 60529, which is identical to EN 60529 and BS EN 60529. The code is usually given in the form IP45. The first digit gives the protection provided against solid objects or dust and the second digit gives the protection against water. There are six levels of protection against penetration by solid objects or dust and eight levels of protection against ingress by water. For each level of protection a test is specified.

The tables show the protection offered at each level.

DISCLAIMER: The information shown in this catalogue was correct at the time of printing.

We reserve the right to alter specifications without notice in the continuance of improving our product and/or to meet new standards.

IEC 60309-2 PRODUCTS TERMINAL CAPACITY

The following table shows the Terminal Capacity of Plugs, Sockets, Connectors and Appliance Inlets manufactured to IEC 60309-2 shown within this catalogue.

1 Terminals for pilot conductors are the same as those for 16A accessories exceeding 50V.

RATING OF THE ACCESSORY TERMINAL CAPACITIES 1
VOLTAGE
CURRENT
A
FLEXIBLE CABLES FOR PLUGS AND CONNECTORS SOLID OR STRANDED CABLES FOR APPLIANCE INLETS AND SOCKET OUTLETS
SERIES I SERIES II mm2 mm2
Not exceeding 16 20 4 to 10 4 to 10
50 32 30 4 to 10 4 to 10
16 20 1 to 2.5 1.5 to 4
Exceeding 32 30 2.5 to 6 2.5 to 10
50 63 60 6 to 16 6 to 25
125 100 16 to 50 25 to 70
First Numeral

Protection against ingress of solid foreign objects.

IP Requirements Example
0 no protection num1.gif - 678 Bytes
1 full penetration of 50mm
diameter sphere not allowed
and shall have adequate
clearance from hazardous
parts. Contact with hazardous
parts not permitted.
num2.gif - 1935 Bytes
2 full penetration of 12.5mm
diameter sphere not allowed.
The jointed finger shall
have adequate clearance
from hazardous parts.
num3.gif - 2661 Bytes
3 the access probe of
2.5mm diameter
shall not penetrate.
num4.gif - 1604 Bytes
4 the access probe of
1.0mm diameter shall
not penetrate.
num5.gif - 1650 Bytes
5 limited ingress of dust
permitted (no harmful
deposit).
num6.gif - 2091 Bytes
6 totally protected against
ingress of dust.
num7.gif - 2229 Bytes

Second Numeral

Protection against harmful ingress of water

IP Requirements Example
0 no protection num1.gif - 678 Bytes
1 protected against vertically
falling drops of water.
Limited ingress permitted.
num8.gif - 2780 Bytes
2 protected against vertically
falling drops of water with
enclosure tilted 15º from
the vertical. Limited
ingress permitted.
num9.gif - 1985 Bytes
3 protected against sprays
to 60º from the vertical
- limited ingress permitted.
num10.gif - 2462 Bytes
4 protected against water
splashed from all directions -
limited ingress permitted.
num11.gif - 1994 Bytes
5 protected against low
pressure jets of water
from all directions -
limited ingress permitted.
num12.gif - 1646 Bytes
6 protected against
strong jets of water.
num13.gif - 2157 Bytes
7 protected against the
effects of immersion
between 15cm and 1m.
num14.gif - 2151 Bytes
8 protected against longer
periods of immersion under
pressure.
num15.gif - 1358 Bytes

The above information kindly supplied by: